Siemens A01590 fault code meaning
Siemens / A01590
Series: DCM-6RA80
Drive: Motor maintenance interval expired
DC drive
Meaning: %1 bin Message class: General drive fault (19). Drive object: CU_DC, CU_DC_R, CU_DC_R_S, CU_DC_S, TM150, TM15DI_DO, TM31. Component: Motor. Broadcast: GLOBAL. Response: None. Acknowledgment: None. Cause: The maintenance interval set for this motor has been reached.
Possible causes
Source: SINAMICS DCM, Parameter Manual, firmware version 1.5 SP2 (based on 5.1 SP2) P978
Series: G110M, G120C, G120D, G120X, G120XA
Drive: Motor maintenance interval expired
converter
Meaning:
Possible causes
Source: SINAMICS G110M P677; SINAMICS G120C P652; SINAMICS G120D Control Unit CU240D- 2_CU250D- 2 P829; SINAMICS G120X Converter P1360; SINAMICS G120XA PN Converter P1275
Series: G115D
Drive: Motor maintenance interval expired
converter
Meaning: The maintenance interval set for this motor has been reached.
Possible causes
Source: SINAMICS G115D P725
Series: G120-CU230P-2, G120P-Cabinet
Motor maintenance interval has elapsed
converter
Meaning:
Possible causes
Source: Converter SINAMICS G120, equipped with control unit CU230P-2 P491; SINAMICS G120P Cabinet P509
Series: G120-CU240B-E-2
Drive: Motor maintenance interval expired
converter
Meaning: The maintenance interval set for this motor has been reached. Warning value (r2124, decimal): Motor data set code. See: p0650 (Current motor operating hours), p0651 (Motor maintenance interval (hours)).
Possible causes
Source: SINAMICS G120 Control Unit CU240B_E-2 P646
Series: G120-CU250S-2
Drive: Motor maintenance interval expired
converter
Meaning: %1 bin Drive object: All objects. Reaction: None. Acknowledgment: None. Cause: The maintenance interval set for this motor has been reached.
Possible causes
Source: SINAMICS G120, Control Unit CU250S-2 P1314
Series: G130-G150
Drive: Motor maintenance interval expired
converter
Meaning: %1 bin Message class: General drive fault (19) Drive object: All objects Component: Motor Broadcast: GLOBAL Reaction: None Acknowledgment: None Cause: The maintenance interval set for this motor has been reached.
Possible causes
Source: SINAMICS G130_G150 P1484
Series: G200
Drive: Motor maintenance interval expired
converter
Meaning: %1 bin Component: Motor. Reaction: None. Acknowledgment: None. Cause: The maintenance interval set for this motor has been reached.
Possible causes
Source: SINAMICS G200 Basic converter P548
Series: S110
Drive: Motor maintenance interval expired
servo drive
Meaning: %1 bin Drive object: SERVO_S110-CAN, SERVO_S110-DP, SERVO_S110-PN. Reaction: None. Acknowledgment: None. Cause: The maintenance interval set for this motor has been reached.
Possible causes
Source: SINAMICS S110 P950
Series: S210
Drive: Motor maintenance interval expired
servo drive
Meaning: The maintenance interval set for this motor has been reached.
Possible causes
Source: SINAMICS S210_SIMOTICS S-1FK2 and S-1FT2 P844