Inovance Err13 fault code meaning

Inovance / Err13

Series: CAN600

Output phase loss

AC drive

Meaning: Loose main circuit output wiring; motor damaged

Possible causes

Source: CAN600 Series AC Drive User Manual Fault Diagnosis P89

Series: CL100, CP320, MD280, MD290, MD300, MD320, MD320N, MD480, MD480P, MD500, MD500E

Output phase loss

AC drive

Meaning:

Possible causes

Source: CL100 Series Integrated Wire Drawing Machine User Manual P35; CP320 Series Air Compressor AC Drive User Manual P48; MD280 Series AC Drive User Manual, Fault Record Parameters P70; MD290 Series General-Purpose AC Drive Quick Start Guide P122; MD300(MD300N) Series AC Drive User Manual, Fault Record Parameters P61; MD320 Series General-Purpose AC Drive User Manual, Fault Record Parameters P73; MD320(MD320N) Series AC Drive User Manual, Fault Record Parameters P77; MD480 Series Industrial Single-Drive AC Drive User Manual P87; MD480P Series AC Drive User Manual P93; MD500 Series General-Purpose AC Drive Commissioning Manual P122; MD500E Series General-Purpose AC Drive User Manual P235

Series: CS280

Output phase loss

AC drive

Meaning: ◆Loose main circuit output wiring ◆Motor damaged

Possible causes

Source: CS280 Series AC Drive for Construction Hoists User Manual Fault Diagnosis P108

Series: MD200, MD310

Output phase loss

AC drive

Meaning: Detection is performed when the run frequency exceeds 0.8Hz. The average current of each of the three output phases is measured, and the ratio of the maximum to the minimum value exceeds 7.

Possible causes

Source: MD200 Series Basic AC Drive User Manual P37; MD310 Series General-Purpose AC Drive User Manual P232

Series: MD210, MD380E

Output phase loss

AC drive

Meaning: Abnormal wiring between the AC drive and motor; AC drive three-phase output imbalance during motor operation; Driver board error; Module error

Possible causes

Source: MD210 Series AC Drive User Manual, Fault Diagnosis P160; MD380E Series AC Drive User Manual, Fault Diagnosis P248

Series: ME320L

Output phase loss protection

elevator controller

Meaning: Loose main circuit output wiring; motor damaged

Possible causes

Source: ME320L Integrated Elevator Controller User Manual, Fault Diagnosis P112

Series: NICE1000, NICE2000ft, NICE3000dt, NICE7000

Output phase loss

elevator controller

Meaning: Loose main circuit output wiring; motor damaged

Possible causes

Source: NICE1000 Series Integrated Elevator Controller User Manual, Fault Diagnosis P79; NICE2000(ft) Door Controller User Manual, Fault Diagnosis P69; NICE3000(dt) Integrated Elevator Controller User Manual, Fault Diagnosis P119; NICE7000 Series Integrated Elevator Controller User Manual, Fault Diagnosis P57