Inovance E140.5 fault code meaning

Inovance / E140.5

Series: MD520

Phase synchronization timeout fault

AC drive

Meaning: The AC drive output phase is controlled by adjusting the frequency to synchronize it with the mains phase: 1, During execution of the phase synchronization state machine, when switching from variable-frequency operation to mains-frequency operation, this fault is reported if |mains phase - AC drive output phase| ≥ D4-34 for a duration ≥ 20s. 2, During execution of the phase synchronization state machine, when switching from mains-frequency operation to variable-frequency operation, this fault is reported if |mains phase - AC drive output phase| ≥ D4-34 for a duration ≥ 10s. 3, During execution of the frequency tracking state machine, this fault is reported if |mains frequency - AC drive output frequency| ≥ 0.5Hz for a duration ≥ 20s.

Possible causes

Source: MD520 Commissioning Manual - Chinese, p. 110

Series: MD520HS-INT, MD520HS

Phase synchronization timeout fault

AC drive

Meaning:

Possible causes

Source: MD520HS-INT Series High-Speed AC Drive User Manual P127; MD520HS Series High-Speed AC Drive User Manual P129