Inovance E093.1 fault code meaning

Inovance / E093.1

Series: MD520

Motor locked rotor fault

AC drive

Meaning: The locked rotor detection threshold is met and the locked rotor detection time has elapsed. Note: Set the locked rotor detection threshold using AA-31/B8-31/BC-73/CC-73 and the locked rotor detection time using AA-32/B8-32/BC-74/CC-74. Enable locked rotor protection using bit 6 of AA-30/B8-30/BC-72/CC-72 Motor protection setting. (Note: The above parameters correspond to the first/second/third/fourth motor parameter groups, respectively.)

Possible causes

Source: MD520 Commissioning Manual - Chinese p. 108

Series: MD520HS-INT, MD520HS, MD600, MD605

Motor locked rotor fault

AC drive

Meaning:

Possible causes

Source: MD520HS-INT Series High-Speed AC Drive User Manual P125; MD520HS Series High-Speed AC Drive User Manual P127; MD600 Series Compact AC Drive User Manual P495; MD605 Series Compact AC Drive User Manual P497