Inovance E045.00 fault code meaning
Inovance / E045.00
Series: MD480-PLUS, MD500-PLUS
Motor overtemperature fault
AC drive
Meaning: The motor temperature transmitted via the AI analog signal exceeds the motor temperature alarm setting.
Possible causes
- Loose temperature sensor wiring
- Motor overtemperature
- F9-57 Motor overtemperature protection threshold setting is too small.
Source: MD480-PLUS Series General-Purpose AC Drive Commissioning Manual P114; MD500-PLUS Series General-Purpose AC Drive Commissioning Manual P699