Inovance E043.2 fault code meaning

Inovance / E043.2

Series: MD520

Synchronous motor FVC runaway fault

AC drive

Meaning: For a synchronous motor or reluctance motor under FVC control, when D6/7/8/9-30 is enabled, the AC drive reports a synchronous motor FVC runaway fault if the actual motor speed is in the same direction as the frequency setting and exceeds the frequency setting by more than the D6/7/8/9-31 threshold for longer than D6/7/8/9-32 (excessive speed deviation detection time); alternatively, the AC drive reports a synchronous motor FVC runaway fault if the actual motor speed is in the opposite direction to the frequency setting and exceeds the D6/7/8/9-31 threshold for longer than D6/7/8/9-32 (excessive speed deviation detection time).

Possible causes

Source: MD520 Commissioning Manual - Chinese p. 102

Series: MD520HS-INT, MD520HS

Synchronous motor FVC runaway fault

AC drive

Meaning:

Possible causes

Source: MD520HS-INT Series High-Speed AC Drive User Manual P120; MD520HS Series High-Speed AC Drive User Manual P122