Inovance E030.00 fault code meaning
Inovance / E030.00
Series: MD480-PLUS, MD500-PLUS
Output load loss
AC drive
Meaning: Asynchronous motor: This fault is triggered during run when the output current is below 25% no-load current and the synchronous frequency is below 90% rated frequency. Synchronous motor: This fault is triggered when the output current is below the load loss current threshold (default: 10%) and either the current reference exceeds the rated current or the output voltage exceeds the detection threshold (detection threshold: 50% × (back EMF +0.25 times the rated voltage)).
Possible causes
- AC drive operating current is below F9-64
Source: MD480-PLUS Series General-Purpose AC Drive Commissioning Manual P112; MD500-PLUS Series General-Purpose AC Drive Commissioning Manual P697