Inovance E013.00 fault code meaning
Inovance / E013.00
Series: MD480-PLUS, MD500-PLUS
Output phase loss
AC drive
Meaning: Detection is performed when the running frequency exceeds 0.8Hz. The average three-phase output currents are measured. A phase loss fault is identified if the ratio of the maximum to the minimum value exceeds 10.
Possible causes
- Motor fault
- Error in the wiring from the AC drive to the motor
- AC drive three-phase output imbalance during motor operation
- Driver board or IGBT module error
Source: MD480-PLUS Series General-Purpose AC Drive Commissioning Manual P95; MD500-PLUS Series General-Purpose AC Drive Commissioning Manual P681