Inovance E006.00 fault code meaning
Inovance / E006.00
Series: MD480-PLUS, MD500-PLUS
Overvoltage during deceleration
AC drive
Meaning: During deceleration, the DC bus voltage exceeds the overvoltage threshold set by A5-09, in units of V.
Possible causes
- Inappropriate overvoltage suppression setting
- An external force drives the motor during deceleration
- Deceleration time too short
- No braking unit or braking resistor is installed.
Source: MD480-PLUS Series General-Purpose AC Drive Commissioning Manual P91; MD500-PLUS Series General-Purpose AC Drive Commissioning Manual P677