Inovance E005.00 fault code meaning
Inovance / E005.00
Series: MD480-PLUS, MD500-PLUS
Overvoltage during acceleration
AC drive
Meaning: During acceleration, the DC bus voltage exceeds the overvoltage threshold set by A5-09, in V.
Possible causes
- Input mains voltage high.
- An external force drives the motor during acceleration
- Inappropriate overvoltage suppression setting
- No braking unit or braking resistor is installed.
- Acceleration time too short
Source: MD480-PLUS Series General-Purpose AC Drive Commissioning Manual P91; MD500-PLUS Series General-Purpose AC Drive Commissioning Manual P677