Inovance A16 fault code meaning
Inovance / A16
Series: HD5X
External communication alarm
AC drive
Meaning: For a slave with A8-00 point-to-point communication enabled, a fault is reported when the CAN communication interruption exceeds 1s
Possible causes
- 1. slave with A8-00 point-to-point communication enabled
- 2. a fault is reported when the CAN communication terminal exceeds 1s
- FD-04 is set to a nonzero value, and the 485 communication interruption exceeds the set time
- The tens digit of FD-05 is set to 5, FD-10 is set to a nonzero value, and the PLC communication interruption exceeds the set time.
- The hundreds digit of FD-05 is set to 1, FD-20 is set to a nonzero value, and the PC communication terminal exceeds the set time.
Source: HD5X Series High-Voltage AC Drive User Manual P102