Delta PGF3 fault code meaning
Delta / PGF3
Series: C2000 Plus
PG feedback stall
AC motor drive
Meaning: In a mode using PG, time accumulation starts when the motor frequency exceeds the encoder stall level (parameter 10-10). If the error duration exceeds the encoder stall detection time (parameter 10-11), a PGF3 PG feedback stall error occurs.
Possible causes
- Incorrect encoder parameter settings
- Parameter 01-00 setting too small
- ASR Related parameters and acceleration/deceleration settings are inappropriate
- Inappropriate parameter settings for the PG feedback stall function. Set parameters 10-10 and 10-11 to appropriate values.
Source: C2000 Plus Series User Manual (DELTA_IA-MDS_C2000 Plus_UM_TC_20250522) P421
Series: C2000-R
PG feedback stall
AC motor drive
Meaning:
Possible causes
Source: C2000-R User Manual P218
Series: CH2000, MH300
PG feedback stall
AC motor drive
Meaning: In a mode with PG, timing starts when the motor frequency exceeds the encoder stall level (parameter 10-10). If the error duration exceeds the encoder stall detection time (parameter 10-11), a PGF3 PG feedback stall error occurs.
Possible causes
- Incorrect encoder parameter settings
- Parameter 01-00 setting too small
- ASR Related parameters and acceleration/deceleration settings are inappropriate
- Inappropriate parameter settings for the PG feedback stall function. Set parameters 10-10 and 10-11 to appropriate values.
Source: CH2000 Series User Manual (DELTA_IA-MDS_CH2000_UM_SC_20251030) P382; MH300 Series User Manual (DELTA_IA-MDS_MH300_UM_TC_20260505) P292
Series: DPD-K
PG feedback stall
AC motor drive
Meaning: In a mode using PG, time accumulation begins when the motor frequency exceeds the encoder stall level (parameter 10-10). If the error duration exceeds the encoder stall detection time (parameter 10-11), a PGF3 PG feedback stall error occurs. (This fault code is not available on DPD-K.)
Possible causes
- Incorrect encoder parameter settings
- Parameter 01-00 setting too small
- ASR Related parameters and acceleration/deceleration settings are inappropriate
- Inappropriate parameter settings for the PG feedback stall function. Set parameters 10-10 and 10-11 to appropriate values.
Source: DPD-K Series User Manual (DPD-K user manual_20211224) P652
Series: MH300-HS
PG feedback stall
AC motor drive
Meaning: In a mode using PG, time starts accumulating when the motor frequency exceeds the encoder stall level (parameter 10-10). If the error duration exceeds the encoder stall detection time (parameter 10-11), a PGF3 PG feedback stall error occurs.
Possible causes
- Incorrect encoder parameter settings
- Parameter 01-00 setting too small
- ASR Related parameters and acceleration/deceleration settings are inappropriate
- Inappropriate parameter settings for the PG feedback stall function. Set parameters 10-10 and 10-11 to appropriate values.
Source: MH300 Series (High-Speed Models) User Manual (DELTA_IA-MDS_MH300-HS_UM_SC_20241213_v3) P252
Series: MS300
PG feedback stall
AC motor drive
Meaning: In a mode using PG, time accumulation starts when the motor frequency exceeds the encoder stall level (parameter 10-10). If the error duration exceeds the encoder stall detection time (parameter 10-11), a PGF3 PG feedback stall error occurs.
Possible causes
- Incorrect encoder parameter settings
- Parameter 01-00 setting too small
- ASR Related parameters and acceleration/deceleration settings are inappropriate
Source: MS300 Series User Manual (DELTA_IA-MDS_MS300_UM_TC_20260417_v2) P246