Delta ALB86 fault code meaning
Delta / ALB86
Series: ASDA-H3
Second power supply module - External regenerative resistor overload
servo drive
Meaning: The drive module capacitor discharges to 45 kW or below. Excessive energy in the regenerative resistor connected to the power supply module causes resistor overload.
Possible causes
- Condition: The drive module capacitor discharges to 45 kW or below. Excessive energy in the regenerative resistor connected to the power supply module causes resistor overload. Cause:
- Incorrect regenerative resistor selection or no external regenerative resistor connected.
- Parameter setting error (P8.087, P8.088).
- Other energy (such as interference) is fed back into the power supply module, or the power supply input voltage exceeds the rated allowable voltage.
- Power supply module hardware fault.
Source: ASDA-H3 User Manual (DELTA_IA-ASD_ASDA-H3_UM_SC_20260428) P812