Delta AL003 fault code meaning

Delta / AL003

Series: ASDA-A3

Undervoltage

servo drive

Meaning: 1. The main circuit voltage is below the specified voltage. The default error type for this alarm is warning (Warning). To change it to alarm (Alarm), set P2.066 [Bit 9] to 1. 2. DC Bus voltage is less than P4.024 × √2.

Possible causes

Source: ASDA-A3 User Manual (DELTA_IA-ASD_ASDA-A3_UM_SC_20230515) P1144

Series: ASDA-B3

Undervoltage

servo drive

Meaning: 1. The main circuit voltage is below the specified voltage. The default response to this condition is a warning (Warning). To change it to a fault (Alarm), set P2.066 [Bit 9] to 1. 2.DC Bus voltage is less than P4.024 × √2.

Possible causes

Source: ASDA-B3 User Manual (DELTA_IA-ASD_ASDA-B3_UM_SC_20250108) P883

Series: ASDA-E3

Undervoltage

servo drive

Meaning: 1. The main circuit voltage is below the specified voltage. This alarm defaults to the warning type (Warning). To change it to the alarm type (Alarm), set P2.066 [Bit 9] to 1. 2. DC Bus voltage is less than P4.024× √2.

Possible causes

Source: ASDA-E3 (DELTA_IA-ASD_ASDA-E3_UM_SC_20260313) P608

Series: ASDA-E3C-E

Undervoltage

servo drive

Meaning: 1. main circuit voltage is below the specified voltage. The default classification of this alarm is warning (WARN). To classify it as an alarm (ALM), set P2.066 [Bit 9] to 1. 2.DC Bus voltage is less than P4.024×√2.

Possible causes

Source: ASDA-E3C-E Application Technical Manual (DELTA_IA-ASD_ASDA-E3C-E_UM_SC_20260612) P533

Series: ASDA-E3C-L

Undervoltage

servo drive

Meaning: 1. The main circuit voltage is below the specified voltage. This alarm defaults to warning (WARN). To configure it as an alarm (ALM), set P2.066 [Bit 9] to 1. 2.DC Bus The voltage is less than P4.024 × √2.

Possible causes

Source: ASDA-E3C-L Application Technical Manual (DELTA_IA-ASD_ASDA-E3C-L_UM_SC_20260612) P405

Series: ASDA-H3

Undervoltage

servo drive

Meaning: 1. The main circuit voltage is below the specified voltage. This alarm defaults to warning (WARN). To configure it as an alarm (ALM), set P2.066 [Bit 9] to 1. 2.DC Bus The voltage is less than P4.024 × √2.

Possible causes

Source: ASDA-H3 User Manual (DELTA_IA-ASD_ASDA-H3_UM_SC_20260428) P768

Series: ASDA-W3

Drive module (DM) DC Bus undervoltage

servo drive

Meaning:

Possible causes

Source: ASDA-W3 Series Servo System Application Technical Manual (DELTA_IA-ASD_ASDA-W3_UM_SC_20251226) P711