ABB DC OVERVOLT 直流过压
ABB / DC OVERVOLT
ACS600
直流过压
变频器
故障含义:Intermediate circuit DC voltage is excessive. DC Ch overvoltage trip limit is 1.3 · U1max, where U1max is the maximum value of the mains voltage range. Ch For 400 V units, U1max is 415 V. For 500 V units, C U1max is 500 V. The actual voltage in the intermediate circuit corresponding to the mains Use voltage trip level is 728 V d.c. for 400 V units an 877 V d.c. for 500 V units.
可能原因
检查与处理
资料来源:ACS600 Standard Application Program Firmware Manual (EN, 官网)
ACS800
中间电路直流电压过高
变频器
故障含义:中间电路直流电压过高。
可能原因
检查与处理
资料来源:ACS800 标准应用程序 固件手册 P234