Hitachi / E7
Series: J100-E2
Over. V
AC drive
Meaning: DC smoothing circuit overvoltage | Rapid deceleration; motor forced to rotate by the load; grounding fault. | Increase deceleration time; impossible to apply to continuous regenerative load; check output wiring and motor for grounds.
Possible causes
Source: Hitachi J100-E2 Instruction Manual P10