ABB F11 fault code meaning
ABB / F11
Series: ACS400
Parameter setting mismatch
drive
Meaning: Parameter values are inconsistent: MINIMUM AI1 > MAXIMUM AI1 (parameters 1301, 1302) MINIMUM AI2 > MAXIMUM AI2 (parameters 1304, 1305) MINIMUM FREQ > MAXIMUM FREQ (parameters 2007, 2008) PFC block tries to use IO extension module (NDIO) but the DDCS link is not parameterised properly
Possible causes
Source: ACS400 User's Manual Rev C (EN, official site)
Series: DCS400
Mains Sync Fault
DC drive
Meaning:
Possible causes
Source: DCS400 Manual (EN, official site)