AB F3 fault code meaning

AB / F3

Series: 1305

Power Loss Fault

AC drive

Meaning: DC bus voltage remained below 85% of nominal for longer than 0.500 sec.

Possible causes

Source: Allen-Bradley Bulletin 1305 User Manual Table 6.B Fault Descriptions P6-3~6-8

Series: PowerFlex 40

Power Loss

AC drive

Meaning: DC bus voltage remained below 85% of nominal.

Possible causes

Source: Allen-Bradley PowerFlex 40 User Manual 22B-UM001 Table 4.A Fault Types P4-3~4-5

Series: PowerFlex 400

Power Loss

AC drive

Meaning: The DC bus voltage remained Mon below the value set in parameter 186 [Power Loss Volts] for longer than the time specified in parameter 185 [Power Loss Time]. You can enable/disable this fault with parameter 238 [Fault Config 1] (page 2-28).

Possible causes

Source:

Series: PowerFlex 700H

Power Loss

AC drive

Meaning: The DC bus voltage remained Mon below the value set in parameter 186 [Power Loss Volts] for longer than the time specified in parameter 185 [Power Loss Time]. You can enable/disable this fault with parameter 238 [Fault Config 1] (page 2-28).

Possible causes

Source:

Series: PowerFlex Digital DC (700DC)

Power Failure

DC drive

Meaning: There is a fault in the 24V Control board supply - Pull the plug-in I/O terminal blocks out of the control the voltage is below the permitted value. In most cases the cause is in the external I/O wiring.

Possible causes